Please use this identifier to cite or link to this item:
https://elib.psu.by/handle/123456789/23820
Full metadata record
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Нияковский, А. М. | - |
dc.contributor.author | Москалёнок, Ф. И. | - |
dc.contributor.author | Нияковский, А. А. | - |
dc.date.accessioned | 2019-08-21T12:38:56Z | - |
dc.date.available | 2019-08-21T12:38:56Z | - |
dc.date.issued | 2018 | - |
dc.identifier.citation | Вестник Полоцкого государственного университета. Серия F, Строительство. Прикладные науки. - 2018. - № 16. - С. 110-115. | ru_RU |
dc.identifier.issn | 2070-1683 | - |
dc.identifier.uri | https://elib.psu.by/handle/123456789/23820 | - |
dc.description | A Study of the Factors Leading to the Temperature Excess of Heating Medium Outlet of Plate Hot Water Heat Exchangers in Individual Heating Plants of Residential Buildings A. Niyakovski, F. Moskalionak, A. Niyakovski | ru_RU |
dc.description.abstract | На основании анализа фактических данных о работе блоков горячего водоснабжения в действующих индивидуальных тепловых пунктах жилых зданий, оборудованных пластинчатыми водонагревателями горячего водоснабжения, установлено, что несоответствие мощности водоподогревателей фактической тепловой нагрузке, занижение температуры греющего теплоносителя на входе водоподогревателя и высокая доля циркуляционного расхода в общем расходе нагреваемой воды ведут в неотопительный период при малых величинах водоразбора к росту температуры теплоносителя в обратной магистрали тепловой сети.= Based on the analysis of the factual data on the operation of hot water supply units in the existing individual heating plants of residential buildings equipped with plate hot water heat exchangers, numerical studies of the factors causing the water temperature increase in the return line of the heat network in the non-heating (summer) period are performed. These factors include: non-compliance of the installed capacity of water heaters with the actual consumption of thermal energy, a high proportion of the circulation flow in the total flow of heated water at low values of its consumption, and the reduced temperature of the primary coolant at the inlet of the heat exchanger. | ru_RU |
dc.language.iso | ru | ru_RU |
dc.publisher | Полоцкий государственный университет | ru_RU |
dc.relation.ispartof | Веснік Полацкага дзяржаўнага ўніверсітэта. Серыя F, Будаўніцтва. Прыкладныя навукі | be_BE |
dc.relation.ispartof | Herald of Polotsk State University. Series F, Civil engineering. Applied sciences | en_EN |
dc.relation.ispartof | Вестник Полоцкого государственного университета. Серия F. Строительство. Прикладные науки | ru_RU |
dc.relation.ispartofseries | Серия F. Строительство. Прикладные науки;2018. - № 16 | - |
dc.rights | open access | ru_RU |
dc.subject | Государственный рубрикатор НТИ - ВИНИТИ::ТЕХНИЧЕСКИЕ И ПРИКЛАДНЫЕ НАУКИ. ОТРАСЛИ ЭКОНОМИКИ::Строительство. Архитектура | ru_RU |
dc.subject | Пластинчатые теплообменники | ru_RU |
dc.subject | Горячее водоснабжение | ru_RU |
dc.subject | Индивидуальные тепловые пункты | ru_RU |
dc.subject | Температурный график | ru_RU |
dc.subject | Plate heat exchangers | ru_RU |
dc.subject | Hot water heat supply | ru_RU |
dc.subject | Thermal charts | ru_RU |
dc.subject | Numerical experiment | ru_RU |
dc.title | Исследование факторов, приводящих к завышению температуры греющего теплоносителя на выходе пластинчатых теплообменников в индивидуальных тепловых пунктах жилых зданий | ru_RU |
dc.type | Article | ru_RU |
dc.identifier.udc | 696.4:697.341 | - |
Appears in Collections: | 2018, № 16 |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
110-115.pdf | 216 kB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.